Instruction manual

2-32 / Installation CI-ControlWaveLP
A status of the POST progress is displayed on the FMI/OB Status LEDs. Unless there is a
problem these codes will scroll at a fast rate and won’t be discernable. Successful
completion is indicated by a binary value of 86 on the Status LEDs and with the cold start
menu being displayed on the PC’s screen. Detection of a fault will be indicated by a binary
code on the Status LEDs. Refer to Section 3.4.4 for POST Status Code definition.
From the HyperTerminal Recovery Mode menu (Figure 2-31), press the ‘F’ key to enter
FLASH download. A message will be displayed warning that the FLASH is about to be
erased; press the ‘Y’ key at the prompt. The screen will display dots as the flash devices are
being erased; this could take a few minutes.
Figure 2-31 - HyperTerminal Recovery Mode Menu
5. When the FLASH is ready for download the letter C will be displayed on the screen. In
the HyperTerminal command bar click on Transfer and then Send File…(see Figure 2-
32). In the Send File Dialog Box (see Figure 2-33), select “1KXmodem” for the protocol,
enter the filename of the appropriate .bin file in the format “LPSxxxxx.bin” (where xxxxx
varies from release to release). Click on the Send button to start the download (see
Figures 2-33 and 2-34). When the HyperTerminal Recovery Mode Menu of Figure 2-31
appears, the download has completed.
6. Close the HyperTerminal program. The null modem cable connected between the
ControlWaveLP and the PC can be removed if desired.
7. Set CPU Switch SW2 positions C & D to OFF (OFF = Recovery Mode Disabled & FLASH
Download Disabled). Switch Power OFF and then ON again via the PSSB’s ON/OFF
Switch.