Instruction manual
CI-ControlWaveLP Installation / 2-25
2.4.6.1 Bulk Power Supply Current Requirements
Maximum current requirements for a bulk +12Vdc or bulk +24Vdc power supply used to
power a ControlWaveLP RTU can be determined by use of Table 2-13 or 2-14 respectively.
These tables provide detailed steady state and loop power current requirements.
Table 2-13 - Power Requirements for Bulk 12Vdc Power Supply
COMPONENTS
Base Unit
MAX # of I/O
NOTES
Base CWLP Unit Full Base I/O Without PC/104 AO Module = 269mA
Base CWLP Unit Full Base I/O With PC/104 AO Module = 284mA
Base CWLP Unit No Base I/O Without PC/104 AO Module = 200mA
Base CWLP Unit No Base I/O With PC/104 AO Module = 215mA
DIs 16 Add 9.47mA/Loop - Dry Contact
DOs 8 -
AIs(4-20mA) 8 Add 50mA/Loop
AIs(1-5V) 8 -
HSCs 4 -
PC/104 AO Mod.
(4-20mA)
4 Add 20.8mA/Loop
PC/104 AO Mod.
(1-5V)
4 Add 27mA/Loop - Output @ 5mA
Table 2-14 - Power Requirements for Bulk 24Vdc Power Supply
COMPONENTS
Base Unit
MAX # of I/O
NOTES
Base CWLP Unit Full Base I/O Without PC/104 AO Module = 202mA
Base CWLP Unit Full Base I/O With PC/104 AO Module = 217mA
Base CWLP Unit No Base I/O Without PC/104 AO Module = 146mA
Base CWLP Unit No Base I/O With PC/104 AO Module = 161mA
DIs 16 Add 4.74mA/Loop - Dry Contact
DOs 8 -
AIs(4-20mA) 8 Add 25mA/Loop
AIs(1-5V) 8 -
HSCs 4 -
PC/104 AO Mod.
(4-20mA)
4 Add 20.8mA/Loop
PC/104 AO Mod.
(1-5V)
4 Add 27mA/Loop - Output @ 5mA
2.5 OPERATIONAL DETAILS
ControlWaveLP RTUs are shipped from the factory with firmware that allows the unit to
be configured in conjunction with an IEC 61131 application program. This section provides
information as follows:
- Steps required to download the application load and place the unit into ‘Run’ mode.
- Steps required to download system firmware.
- Operation of the CPU Module’s Reset Switch
- Soft Switch Configurations and Communication Ports