Instruction manual
2-14 / Installation CI-ControlWaveLP
Figure 2-7 - Point-to-Point 10Base-T Ethernet Cable
The maximum length of one segment (CPU to Hub) is 100 meters (328 feet). The use of
Category 5 shielded cable is recommended.
Figure 2-8 - Standard 10Base-T Ethernet Cable (CPU Module to Hub)
Table 2-7 - Ethernet 10/100Base-T CPU Module Pin Assignments
Pin # Description Pin # Description
1 Transmit Data+ (Output) 5 Not Connected
2 Transmit Data- (Output) 6 Receive Data- (Input)
3 Receive Data+ (Input) 7 Not Connected
4 Not Connected 8 Not Connected
Note: TX & RX are swapped at Hub’s.