Instruction manual
2-8 / Installation CI-ControlWaveLP
Table 2-1 - FMI/OB Board Jumper Assignment
Jumper Function Notes
W1 Config. DI1 see Figure 2-6 (2-3 = Isolated DI) (1-2 & 3-4 = Dry Contact DI)
W2 Config. DI2 see Figure 2-6 (2-3 = Isolated DI) (1-2 & 3-4 = Dry Contact DI)
W3 Config. DI3 see Figure 2-6 (2-3 = Isolated DI) (1-2 & 3-4 = Dry Contact DI)
W4 Config. DI4 see Figure 2-6 (2-3 = Isolated DI) (1-2 & 3-4 = Dry Contact DI)
W5 Config. DI5 see Figure 2-6 (2-3 = Isolated DI) (1-2 & 3-4 = Dry Contact DI)
W6 Config. DI6 see Figure 2-6 (2-3 = Isolated DI) (1-2 & 3-4 = Dry Contact DI)
W7 Config. DI7 see Figure 2-6 (2-3 = Isolated DI) (1-2 & 3-4 = Dry Contact DI)
W8 Config. DI8 see Figure 2-6 (2-3 = Isolated DI) (1-2 & 3-4 = Dry Contact DI)
W9 Config. DI9 see Figure 2-6 (2-3 = Isolated DI) (1-2 & 3-4 = Dry Contact DI)
W10 Config. DI10 see Figure 2-6 (2-3 = Isolated DI) (1-2 & 3-4 = Dry Contact DI)
W11 Config. DI11 see Figure 2-6 (2-3 = Isolated DI) (1-2 & 3-4 = Dry Contact DI)
W12 Config. DI12 see Figure 2-6 (2-3 = Isolated DI) (1-2 & 3-4 = Dry Contact DI)
W13 Config. DI13 see Figure 2-6 (2-3 = Isolated DI) (1-2 & 3-4 = Dry Contact DI)
W14 Config. DI14 see Figure 2-6 (2-3 = Isolated DI) (1-2 & 3-4 = Dry Contact DI)
W15 Config. DI15 see Figure 2-6 (2-3 = Isolated DI) (1-2 & 3-4 = Dry Contact DI)
W16 Config. DI16 see Figure 2-6 (2-3 = Isolated DI) (1-2 & 3-4 = Dry Contact DI)
W17 DI LEDs Installed = DI LEDs Enabled
W18 DO LEDs Installed = DO LEDs Enabled
W20A Config. AI1 see Figure 2-11
W20B Config. AI1 see Figure 2-11
W21A Config. AI2 see Figure 2-11
W21B Config. AI2 see Figure 2-11
W22A Config. AI3 see Figure 2-11
W22B Config. AI3 see Figure 2-11
W23A Config. AI4 see Figure 2-11
W23B Config. AI4 see Figure 2-11
W24A Config. AI5 see Figure 2-11
W24B Config. AI5 see Figure 2-11
W25A Config. AI6 see Figure 2-11
W25B Config. AI6 see Figure 2-11
W26A Config. AI7 see Figure 2-11
W26B Config. AI7 see Figure 2-11
W27A Config. AI8 see Figure 2-11
W27B Config. AI8 see Figure 2-11
W28 Power Loop power for DIs & HSC (Installed)
W29 Power Loop Power for AIs (Installed)
W30 Status LEDs Installed = STATUS LEDs Enabled
W31 Comm. LEDs Installed = COMM. LEDs Enabled
W32 Config. HSC1 see Figure 2-15 (Installed = Debounce Circuit Enabled)
W33 Config. HSC1 see Figure 2-15 (2-3 = Isolated) (1-2 & 3-4 = Field Powered HSC)
W34 Config. HSC2 see Figure 2-15 (Installed = Debounce Circuit Enabled)
W35 Config. HSC2 see Figure 2-15 (2-3 = Isolated) (1-2 & 3-4 = Field Powered HSC)
W36 Config. HSC3 see Figure 2-15 (Installed = Debounce Circuit Enabled)
W37 Config. HSC3 see Figure 2-15 (2-3 = Isolated) (1-2 & 3-4 = Field Powered HSC)
W38 Config. HSC4 see Figure 2-15 (Installed = Debounce Circuit Enabled)
W39 Config. HSC4 see Figure 2-15 (2-3 = Isolated) (1-2 & 3-4 = Field Powered HSC)
W40 HSC LEDs Installed = HSC LEDs Enabled
W41
MC/PFIN LEDs
Installed = /MC and/PFIN LEDs Enabled
JP2 AI Config. (1-2 = Shield to Isolated AI Gnd.) (2-3 = AI Shield to GNDEARTH)
JP3 HSC Config. (1-2 = Shield to Isolated Ground) (2-3 = Shield to GNDEARTH)
JP4 Sys. Clock 1-2 = 6 MHz System Clk. (Synchronous to Bus Cycle) (see 2-3 below)