Instruction manual
1-20 /Introduction ControlWaveLP
FMI/OB Bd. Connectors TB5 - TB8 PC/104 I/O & P3 - P6 I/O Expansion Interface
FMI/OB Cable Connectors P3, P4, P5 and P6 are provided to interface a PC/104 Expansion
Board to Expansion I/O Terminal Blocks TB5 through TB8 respectively. Ribbon Cable(s)
will be used to interconnect a PC\104 Expansion Board to P3, P4, P5 & P6.
FMI/OB Bd. PC/104 Bus Connectors P7 & P10 (CPU/FMI/OB Interface)
Connections to the ISA bus are available on the PC/104 bus via the CPU/FMI/OB Interface
Connectors P7 and P10 (J10 of CPU mates with P7 of FMI/OB and J11 of CPU mates with
P10 of FMI/OB) (see Table 4-10). With the exception of FMI/OB Board signal P10-1 (PFIN*)
and CPU Board signal J11-1 (PWR_FAIL) all signals are identical. ISA bus signals are
provided by the RadiSys R400EX system controller on the CPU Board.
During non-ISA bus cycles, the R400 places the ISA bus into a quiet mode to reduce overall
power consumption. The external interface to PC/104 cards is level shifted to a 5V bus
through a set of buffers and transceivers and is capable of driving up to 8 PC/104 cards.
FMI/OB Bd. Power Supply/Sequencer Bd. (PSSB) Interface Connector P9
Connector P9 is a 20-pin DIP Header that interfaces Power, Ground and power supply
status signals to Connector J1 on the PSSB Board (see Table 4-11).
1.3.3.3 FMI/OB Board Jumpers
The FMI/OB Board contains 52 Configuration Jumpers (situated on the top side of the
PCB) (see Table 1-10).
It should be noted that although JP1 appears to be a Jumper Block, it is actually used for
measuring voltages as follows:
+5V - measure between JP1-1(+) and JP1-2(-)
+1V - measure between JP1-3(+) and JP1-2(-)
Table 1-10 - FMI/OB Board Jumper Assignment
Jumper Function Notes
W1 Config. DI1 see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI)
W2 Config. DI2 see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI)
W3 Config. DI3 see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI)
W4 Config. DI4 see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI)
W5 Config. DI5 see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI)
W6 Config. DI6 see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI)
W7 Config. DI7 see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI)
W8 Config. DI8 see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI)
W9 Config. DI9 see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI)
W10 Config. DI10 see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI)
W11 Config. DI11 see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI)
W12 Config. DI12 see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI)
W13 Config. DI13 see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI)
W14 Config. DI14 see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI)
W15 Config. DI15 see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI)
W16 Config. DI16 see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI)
W17 DI LEDs Installed = DI LEDs Enabled
W18 DO LEDs Installed = DO LEDs Enabled
W20A Config. AI1 see Figure 2-11