Instruction manual
CI-ControlWaveLP Appendix 1 Page 9 PC-104 AO Module Option
Table 2 - PC/104 AO Board Connector P3 and FMI/OB PC/104 Connectors
Wiring Summary (Continued)
FMI/OB
TB5/6/7/8
Assignment
AO Bd. P3
FMI/OB
P3/4/5/6
Pin #
Signal Description
23 18 ISORET AO Isolated Ground
24 17 ISORET AO Isolated Ground
25 16 ISORET AO Isolated Ground
26 15 ISORET AO Isolated Ground
27 14 ISORET AO Isolated Ground
28 13 ISORET AO Isolated Ground
29 12 V EXT RET External Power Return
30 11 V EXT RET External Power Return
31 10 V EXT+ 9 - 30 Vdc External Voltage Source
32 9 V EXT+ 9 - 30 Vdc External Voltage Source
- 8 ISORET Analog Output Isolated Ground
- 7 ISORET Analog Output Isolated Ground
- 6 VIN Field Power from FMI/OB
- 5 VIN Field Power from FMI/OB
- 4 PSGND Field Power Return
- 3 PSGND Field Power Return
- 2 CHASSIS Chassis Ground
- 1 CHASSIS Chassis Ground
Terminal Connections
The ControlWaveLP uses compression-type terminals that accommodate up to #16 AWG
wire. A connection is made by inserting the wire’s bared end into the clamp beneath the
screw and securing the screw. The wire should be inserted fully so that no bare wires are
exposed to cause shorts. If using standard wire, tin the bare end with solder to prevent
flattening and improve conductivity.
Allow some slack in the wires when making terminal connections. The slack makes the con-
nections more manageable and minimizes mechanical strain on the terminal blocks.
Signal Shielding and Grounding
The use of twisted-pair, shielded and insulated cable for analog output signal wiring will
minimize signal errors caused by electromagnetic interference (EMI), radio frequency
interference (RFI) and transients. When using shielded cable, all shields should only be
grounded at one point in the appropriate system. This is necessary to prevent circulating
ground current loops that can cause signal errors.
SPECIFICATIONS
Performance Specifications
Number of Analog Outputs: 4