Instruction manual
ControlWave ExpressPAC Instruction Manual (CI-ControlWave EPAC)
1. Start OpenBSI communications using NetView, TechView, or
LocalView, and select the RTU you want to test.
2. Select Start >Programs > OpenBSI Tools >Common Tools >
Diagnostics. The Main Diagnostics menu (Figure 5-6) opens.
Figure 5-6. WINDIAG Main Diagnostics Menu
3. Select the component to be tested. See Section 5.3.4 for a
description of the tests. Enter any prompted parameters (slot #,
etc.). WINDIAG performs the diagnostics and displays pass/fail
results.
After performing all diagnostic testing, exit WINDIAG.
4. Set switches SW2-3 and SW2-8 on the CPU module to ON. The
ControlWave ExpressPAC should resume normal operation.
5.3.4 Available Diagnostics
WINDIAG’s Main Diagnostics Menu (see Figure 5-6) provides the
following diagnostic selections:
Option Tests
CPU & Peripherals Checks the CPU/System Controller board except
for memory.
Analog Output Checks the AO on the Process I/O board.
High Speed Counter Checks HSCs on the Process I/O board and
5-12 Service & Troubleshooting Revised Mar-2011