Instruction manual
ControlWave Express Instruction Manual (CI-ControlWave Express)
1. Connect a null modem cable between COM1 of the
ControlWave Express and any RS-232 port on the associated
PC.
2. Click Start > Programs > Accessories > Communications >
HyperTerminal
3. If using HyperTerminal for the first time, set the communication
properties (for the PC port) via the Properties Menu as follows:
Bits per second: = 115200, Data bits: = 8, Parity: = None, Stop
bits: = 1, and Flow control: = None and then click OK.
4. Set CPU/System Controller board switch SW1-3 ON (ON =
Force Recovery).
5. Apply power; to the ControlWave Express. The resident BIOS
initializes and tests the hardware, this process is referred to as
POST (Power On Self Test). Unless there is a problem, status
LEDS show status code 10 (LED #5 ON). If you see a different
status code, see Section 5.3.1.
6. From the HyperTerminal Mode menu (Figure 5-1), press the F
key to enter FLASH download. A message warns that the
FLASH is about to be erased; press the Y key at the prompt. The
screen displays dots as the system erases the flash memory; this
could take a few minutes.
Figure 5-1. HyperTerminal Mode Menu
7. When the FLASH is ready for download, HyperTerminal
repeatedly displays the letter C on the screen. In the
HyperTerminal menu bar click Transfer > Send File (see
Figure 5-2).
Revised Mar-2011 Service & Troubleshooting 5-3