Brochures and Data Sheets
Industrial Power for
Business-Critical Continuity
™
Chloride BMS
Battery Monitoring System
Sentinel data acquisition module - technical data
Purpose
The Sentinel module allows to measure string values and makes data acquisition from the connected m-Senzors.
Battery string measured values
String voltage range 2V - 600V
String current:
•Measurement Range 0A - 2000A
•Number of string current measures up to 5 (scaleable to 16)
String ambient temperature:
•Measurement range 0°C to 50°C
•Number of measures up to 5. Only 1 sensor per battery room if several strings in
the same battery room
Acquisition of battery monoblock measured values
Number of monoblocks
(1)
up to 160 (scaleable to 1280)
Voltage (depending on battery type and m-Senzor type) from 1V to 12V
Impedance
(2)
(depending on block voltage and m-Senzor) from 0.15 to 40 mΩ - For Lead Acid batteries ONLY
Temperature
(2)
from -10°C to +70°C
General Data
Power supply voltage range 48 VDC - 110 VDC
Dimensions Height: 270mm (1U)
Width: 430mm
Depth: 45mm
Communication
LEDs 12 status LEDs on front of the module
Service port RS232 for confi guration / factory setting)
Digital inputs 4
(1)
A monoblock represents one or more battery cells in a container.
(2)
Available as option.
m-Senzor module technical data
Purpose
m-Senzor is the measurement module which can measure individual monoblock voltage, impedance and temperature.
Application Lead Acid or Nickel-Cadmium
Vented or Recombination
Measurements
Input confi guration Single or Dual monoblocks sensors
Nominal voltage 1 V 2 V 4 V 6 V 8V 12 V
Voltage measure 0.8V - 1.9V 1.6V - 2.6V 3.2V - 5.2V 4.8V - 7.8V 6.4V - 10.4V 9.6V - 15.6V
Impedance measure 0.15 - 5 mΩ 0.15 - 5 mΩ 0.15 - 5 mΩ 0.5 - 20 mΩ 0.5 - 20 mΩ 1 - 40 mΩ
Temperature measure -10°C to +70°C (measure taken on negative post of battery)
General Data
Power supply powered by the monoblocks being monitored
Interface to Sentinel BBUS (150m max cable length per BBUS port)
Link Battery Management Software
Purpose
Link is the battery management software which allows easy interfacing and understanding of battery status and alarms
Recommended PC system requirements
(3)
Processor Intel E5400 DUAL CORE or better
Operating system Windows XP Professional or greater
RAM 2 GB
(3)
PC is not part of our scope of supply.
Sentinel module
m-Senzor module
Chloride BMS Box - technical data
Purpose
The Chloride BMS box is a wall-mounted box to interconnect the monitored battery with the monitoring software tool
and which allows remote indication via serial link and volt-free contacts.
General Data
Power supply voltage range 48VDC - 400VDC (from battery)
Dimensions Height: 560mm
Width: 585mm
Depth: 400mm
Ingress protection IP42 according to IEC60529
Frame colour Grey RAL 7032
Cable entry Bottom
Operating temperature 0°C to 50°C
Storage temperature 0°C to 70°C
Communication
Relay outputs (volt-free contacts) -Voltage fault
-Temperature fault
-Impedance fault
-System fault
Com port 1 Ethernet
Com port 2 RS 485 interface: Modbus ASCII or RTU protocol
Chloride BMS box
Link software screenshot
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity™.
Emerson, Business-Critical Continuity and
Emerson Network Power are trademarks of
Emerson Electric Co. or one of its affi liated companies.
©2012 Emerson Electric Co.
BMS-DSUK-Rev0-12/2012
AC Power
Connectivity
DC Power
Infrastructure Management & Monitoring
Outside Plant
Power Switching & Controls
Embedded Computing
Embedded Power
Industrial Power
Precision Cooling
Racks & Integrated Cabinets
Services
While every precaution has been taken to ensure the accuracy and completeness of this literature, Emerson Network power assumes no responsability and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
Emerson Network Power IS S.A.S
30 avenue Montgolfi er - BP90 - 69684 Chassieu Cedex - France
T: +33 (0)4 78 40 13 56 F: +33(0)4 78 90 58 90
Industrial.sales.Chloride@Emerson.com
EmersonNetworkPower.com