Installation and Use Manual
Installation
2
1.0 INSTALLATION
The NetSure
™
RDB Rack PDUs (Power Distribution Units) are designed to be installed on the left
and/or right rear frames of IT racks. They can be mounted directly to the rack or use Rack PDU
Mounting Kit P/N 547665. See 3.4 - Dimensions for hole dimensions.
1.1 Shipment Inspection
Unpack the shipping container, inspect all items for damage and verify that the shipment is complete
and undamaged. Report any damage to your local Emerson representative and the carrier.
1.2 Installing the Rack PDU
1.2.1 Installing the Rack PDU Directly to a Rack Frame or Existing Mounting Bracket
Install the Rack PDU directly to the rack frame or existing mounting bracket as shown in Figure 1.
Note that the supplied "Ground Lead Bracket" is to be placed between the PDU and the rack frame or
existing mounting bracket as shown in Figure 1. Use the supplied 1/4-20 screws and 1/4-20 KEPS
nuts.
1.2.2 Installing Rack PDUs to a Rack Frame using the Optional Mounting Bracket
If using the Rack PDU Mounting Kit, install the Rack PDU mounting bracket to the left and/or right
rear frame of the rack using the appropriate hardware that fits to the cabinet that will be used.
Install the Rack PDUs to the Rack PDU mounting bracket that was previously installed on the frame
as shown in Figure 2. Note that the supplied "Ground Lead Bracket" is to be placed between the
PDU and the mounting bracket as shown in Figure 2.
!
WARNING
Ensure proper grounding.
The Rack PDU’s "Ground Lead Bracket" must be ground bonded to the mounting bracket (if
used) or rack frame. The mounting bracket (if used) must be ground bonded to the rack frame.
The rack frame must be ground bonded to your site ground. This is typically accomplished
through the use of paint free areas and/or grounding washers used when mounting the
components.