Installation and Use Manual

Specifications and Technical Data
8
3.4.2 NetSure
RDB L15, P/Ns 547694, 547695, 547615
Detail B, DC Input Cable Assembly
1/0 AWG Cables
72
(1828.80)
350A Anderson, PP350
Powerpole Connector,
Red
DC Input Cable Assembly
(factory supplied and connected)
See Detail B.
Front View
Top View
Bottom View
Right Side View
0.28 (7.11) x 0.50 (12.70)
slot
0.28 (7.11) dia.
Left Side View
3.10
(78.74)
3.00
(76.20)
0.40
(10.16)
30.83
(783.08)
31.63
(803.40)
1.25
(31.75)
Notes:
1. Dimensions are in inches (millimeters),
unless otherwise specified.
2. Includes hardware to mount PDU
to IT rack or bracket P/N 547604.
3. Rack PDU and/or Ground Lead Bracket
can be mounted either as shown or
180 degree rotate.
4. Fifteen outlets.
DC Output
Cable Assembly
P/N 547595 or P/N 555654
(separately ordered,
see 3.6.1)
Circuit Breaker Alarm Connector
(mating screw-type connector supplied,
wire size range 16-24 AWG,
recommended torque 1.8 in-lbs)
Ground wires
factory connected to
Ground Lead Bracket.
(ground wires not shown)
See Detail A.
Local Circuit Breaker
Open Alarm Indicator
Detail A, Ground Lead Jumper
Tyco Electronics
Mate-N-Lok Connector, 350866-1
with 350922-3 male pin
Factory Connected to
Ground Lead Bracket
Jumper Length: 3 (76)
10 AWG Cable