Installation and Use Manual

Specifications and Technical Data
6
3.0 SPECIFICATIONS AND TECHNICAL DATA
3.1 Conformity and Standards
The NetSure RDB Rack PDU (Power Distribution Unit) has the following agency approval ratings:
UL 60 950-1 + UL 1801 - Recognized (cURus)
3.2 Environmental Characteristics
The NetSure RDB Rack PDU (Power Distribution Unit) is designed to operate under the following
environmental conditions without damage or degradation in electrical operating characteristics:
3.3 Specifications
1
Max Amps rated at end of battery discharge (42V).
2
PDU power rating limited to 200A, 8.4kW each.
Operating Temperature
-40°F to +104°F (-40°C to +40°C) (Models L6 and L15).
-40°F to +113°F (-40°C to +45°C) (Models H2, H3, and M6).
Storage Temperature -40°F to +176°F (-40°C to +80°C).
Relative Humidity 0 to 95%, non-condensing.
Operating Elevation 6562 ft (2000m) at full power.
Model
Part
Number
Number
of
Outlets
Power Rating per Outlet Power Rating per PDU Input/Output
Voltage
(nominal)
RDB - Basic Rack PDUs
Max Watts Max Amps
1
Max kW Max Amps
1
L6
547692
6
420 10 2.5 60
-48Vdc
547693 630 15 3.8 90
547499 840 20 5.0 120
L15
547694
15
420 10 6.3 150
547695 630 15 8.4
2
200
2
547615 840 20 8.4
2
200
2
M6
547696
6
1050 25 6.3 150
547697 1260 30 7.6 180
547503 1470 35 8.4
2
200
2
H2 547500 2 3360 80 6.7 160
H3
547698
3
2100 50 6.3 150
547699 2520 60 7.6 180
547501 2940 70 8.4
2
200
2