Data Sheet
2 128DRA-NSRDB / 0214
NetSure
™
RDB Series
Ordering Information
Model Part Number Number of Outlets Power Rating per Outlet Power Rating per PDU
RDB - Basic Rack PDUs
Max Watts Max Amps
1
Max kW Max Amps
1
L6
547692
6
420 10 2.5 60
547693 630 15 3.8 90
547499 840 20 5.0 120
L15
547694
15
420 10 6.3 150
547695 630 15 8.4
2
200
2
547615 840 20 8.4
2
200
2
M6
547696
6
1,050 25 6.3 150
547697 1,260 30 7.6 180
547503 1,470 35 8.4
2
200
2
H2 547500 2 3,360 80 6.7 160
H3
547698
3
2,100 50 6.3 150
547699 2,520 60 7.6 180
547501 2,940 70 8.4
2
200
2
1
Max Amps rated at end of battery discharge (42 V).
2
PDU power rating limited to 200 A, 8.4 kW each.
Item Part Number Description
Accessories
Rack Mounting Bracket 547665 Attachment point for NetSure
™
RDB for racks without built-in mount, fits either left or right.
Output Cable – Low, 6’ 547595 Output power cord for L6, L15, M6 models, 6' long, order 1 for every outlet used
Output Cable – Low, 10’ 555654 Output power cord for L6, L15, M6 models, 10' long, order 1 for every outlet used
Output Cable – High, 4' 547613 Output power cord for H2, H3 models, 4' long, order 1 for every outlet used
Output Kit – Low 554878 Mating output connector and contacts for 10 to14 AWG and 12 AWG to 16 AWG wires
Output Kit – High 554944 Mating output connector and contacts for 6 AWG, 8 AWG, and 10 AWG to 12 AWG wires
1/0 Input Kit * 547668 Mating input quick connector, 1/0 wire
2/0 Input Kit * 547669 Mating input quick connector, 2/0 wire
3/0 Input Kit * 547670 Mating input quick connector, 3/0 wire
4/0 Input Kit * 547671 Mating input quick connector, 4/0 wire
* Select (1) per PDU, depending on input wire size.
Application
Rack-Mount Server Applications
NetSure
™
RDB L6
Low power
(up to 840 W per outlet)
6 outlets
NetSure
™
RDB L15 15 outlets
NetSure
™
RDB M6
Medium power
(up to 1470 W per outlet)
6 outlets
Blade Server or High Capacity Switch Applications
NetSure
™
RDB H2
High power
(up to 3360 W per outlet)
2 outlets
NetSure
™
RDB H3 3 outlets