User Guide
28.....Avocent® ACS6000 Advanced Console Server
--:#- [serial_ports/physical] cli->
4. Enter set status=enabled, then enter show and save as shown to enable the configured
port and verify and save the configuration.
--:- serial_ports/physical cli-> set status=enabled
--:- serial_ports/physical cli-> show
--:- serial_ports/physical cli-> save
To enable a power management port:
1. Log onto the CLI as an administrator and enter set_power ports/serial_ports/ <port
number> to select a port with a PDU connected (port 3 is used as an example).
--:- / cli-> set_power ports/serial_ports/ 3
2. Enter show to view the configuration of port 3.
--:- serial_ports/physical cli-> show
Selected items: 3
Port: 3
enable_cisco_rj45_pin-out = no
status = enabled
speed = 9600
parity = none
data_bits = 8
stop_bits = 1
flow_control = none
Type ls to see available sub-nodes
--:- serial_ports/physical cli->
3. Enter set status=enabled then enter save to set the Serial_Profile to Power, enable the
port and commit the changes.
4. Enter show to verify the configuration.
--:- serial_ports cli-> show
Port Device Name Profile Settings
==== ====== ================== ======= =========================
1 ttys1 ACS6016-0088664422 cas 9600_8N1_telnet-ssh_local
2 ttys2 21-67-72-p-2 cas 9600_8N1_telnet-ssh_local
3 ttys3 power cas 9600_8N1_telnet-ssh_local