User Guide
Administration.....87
or log files.
You can set up logging of messages for the following types of events:
• Events of interest from the appliance
• Sensor alarms generated by sensors on SPs
Messages can be sent to a user defined destination.
Message filtering levels
Messages can be filtered according to their severity, based on any or all of the levels from the
following list:
• Emergency
• Alert
• Critical
• Error
• Warning
• Notice
• Info
• Debug
To configure syslog message filtering:
1. From the sidebar, go to Monitoring. From the drop-down list, choose the Facility.
2. Under the Notification Rules heading, check the boxes for the events for which you want to
receive syslog alerts and click Apply.
3. From the sidebar, go to Monitoring - Notification Destinations and under the Syslog heading,
click Configure next to the rule you want to configure.
4. On the Syslog Rules page under the Configure Syslog Rule, enter the Destination. The
destination can be an IP address or a log file name.
5. The Tag field is optional and will filter messages that do not match the Tag string.
6. Under the Facility heading, use the arrows to select the local facilities.
7. Under the Severity heading, use the arrows to select the severity.
8. Click Apply.
Digital Output
The digital outputs are remote controlled relay ports. These ports, labeled DO1/DO2 on the back of
the appliance, can be used to open or close an electric circuit that can drive sirens, lights and locks.