User Guide
84.....Avocent® Universal Management Gateway Appliance Installer/User Guide
Digital inputs
The digital inputs collect smoke, leak and motion data. They can be connected to the DI1/DI2 ports
on the back of the appliance.
Property Description Default Value
Sensor # Sensor ID (Read Only) System Defined Value
Enabled Enable or Disable Enabled
Name Name of the sensor Sensor ID
Default State Closed or Open Open
Location The sensor's location or position Blank
Type Type of sensor: Custom, smoke, leak or motion Custom
Address The serial number of the sensor (Read Only) Information from Sensor
Digital Input Properties
To detect, enable/disable or edit a OneWire digital input sensor:
1. Click Administration - Sensors - Digital Input.
2. Click Detect to search for new sensors.
3. Click the sensor number, choose the type of sensor or update the normal status.
4. Click Enable to enable or disable the sensor.
Environment
Environment sensors collect temperature and humidity data. They can be connected to the
TH1/TH2 ports on the back of the appliance.
Property Description Default Value
Enabled Enable or Disable Enabled
Name Name of the sensor Sensor ID
Type Temperature or Humidity (Read Only) Temperature
Address The serial number of the sensor (Read Only) Information from Sensor
Location User defined location of the sensor Blank
Environment Sensor Properties
To detect, enable/disable or edit an environment sensor:
1. Click Administration - Sensors - Environment Sensor.
2. Click Detect to search for new sensors.
3. Click the sensor number and then click Enable or Disable to enable or disable the sensor.