User Guide

Administration.....83
Number Name Type
2 DO2 (Digital Output) Buzzer, Beacon and Door Lock
3 DI1/DI2 (Digital Input) Vibration, Smoke, Leak, Door and Motion
4 TH1/TH2 (1-Wire) Temperature, Humidity and Dry Contacts
The following table displays the data that can be collected.
Measurement Units
Temperature Celsius/Fahrenheit
Humidity % RH
Door Status Active/Inactive
Leak Status Active/Inactive
Motion Status Active/Inactive
Vibration Status Active/Inactive
Smoke Status Active/Inactive
Environmental Measurements
Com Digital Input
The COM digital input (DI) sensors view and monitor motion and smoke. They can be connected to
the DI1/DI2 ports on the back of the appliance.
Property Description Default Value
Sensor # Sensor ID (Read Only)
System Defined
Value
Enabled Enable or Disable Enabled
Name Name of the sensor Sensor ID
Type
Smoke, Door, Leak or Motion. Sensor type can only be selected when the
sensor is added.
Smoke
Default
State
Open or Closed Open
Location The sensor's location or position Blank
COM Sensor Properties
To add, enable or remove a COM digital input sensor:
1. Click Administration - Sensors - COM Digital Input.
2. Enter the name of the sensor.
3. Select the port (DI1 or DI2).
4. Select the type of sensor and click Add.
5. Click the sensor name, choose the normal status and click Enable.