User Guide

18.....Avocent® Universal Management Gateway Appliance Installer/User Guide
Number Description Number Description
2 Ethernet connection 12 Remote authentication
3 User 13 PCclient
4 External sensors connection 14 USB media
5
Autosensing ports for serial or service
processor targets
15 RJ-45 serial setup port
6 UMIQ modulefor KVMconnection 16 DB9 com port
7 Target server (VGA/USB) 17 PCfor local configuration
8 Firewall 18
USBconnection (keyboard, mouse
or media)
9 Ethernet connection 19 VGAconsole port
10 Local Area Network (LAN) 20
LCDtray for local configuration
and access
Using Telnet or SSH to access a serial target
An authorized user can use a Telnet or SSH client to make a connection directly to the console of a
serial target if all of the following are true.
The Telnet or SSH:
protocol is enabled for network service in the security profile
protocol is configured for the port
client is available, and it is enabled on the computer from which the connection is made
To use Telnet to connect to a target through a serial port:
For this procedure, you need the username configured to access the serial port, the target name
(for example, 14-35-60-p-1), device name (for example, ttyS1), TCP port alias (for example, 7001)
and the hostname of the appliance or its IP address.
To use a Telnet client, enter the information in the dialog boxes of the client.
-or-
To use Telnet in a shell, enter the following command:
# telnet [hostname | IP_address]
login: [username]:[targetname | device_name]
-or-
# telnet [hostname | IP_address] TCP_Port_Alias
login: [username]
To close a Telnet session:
Enter the Telnet hotkey defined for the client. The default is Ctrl + q to quit.