User Guide
8.....Avocent® Universal Management Gateway Appliance Installer/User Guide
Bracket Connections for Rack Mount Configuration
Rack mount safety considerations
• Elevated Ambient Temperature: If installed in a closed rack assembly, the operating
temperature of the rack environment may be greater than room ambient. Use care not to
exceed the rated maximum ambient temperature of the appliance.
• Reduced Air Flow: Installation of the equipment in a rack should be such that the amount of
airflow required for safe operation of the equipment is not compromised.
• Mechanical Loading: Mounting of the equipment in the rack should be such that a hazardous
condition is not achieved due to uneven mechanical loading.
• Circuit Overloading: Consideration should be given to the connection of the equipment to the
supply circuit and the effect that overloading of circuits might have on overcurrent protection
and supply wiring. Consider equipment nameplate ratings for maximum current.
• Reliable Earthing: Reliable earthing of rack mounted equipment should be maintained. Pay
particular attention to supply connections other than direct connections to the branch circuit
(for example, use of power strips).
Wall mounting
NOTE: The wall-mounting kit is optional and is not included with the appliance; it must be purchased
separately. For details on how to purchase the wall-mounting kit, contact your Avocent representative.
To wall mount the appliance:
1. Using the slots on the bracket or the supplied template as a guide, mark the holes in the
plywood wall where the brackets are to be fastened. A minimum of two holes for each bracket