User's Manual

2. Click Units in the top navigation bar.
3. Click Power Manager or Infrastructure in the side navigation bar.
4. To modify thresholds for a unit, click on the name of a row of racks, rack or power device.
The Unit Overview window opens. Click Power Manager in the side navigation bar.
-or-
To modify thresholds for multiple units of the same type at once, select the row of
racks, rack or power device from the list and click Configure Thresholds from the
Operations menu.
5. Specify the threshold values for total current, power consumption, internal/external
temperature, relative humidity, phase/circuit current and phase/circuit power consumption
in the fields provided. For each category, enter the following values:
•High Critical - When the actual rating is above this value, a high critical alarm is
sent.
•High Warning - When the actual rating is above this value, a high warning alarm is
sent. This alarm is designed to indicate when the value is approaching a critical level,
so it is recommended that the high warning value be slightly lower than the high
critical value.
•Low Warning - When the actual rating is below this value, a low warning alarm is
sent. This alarm is designed to indicate when the value is approaching a critical level,
so it is recommended that the low warning value be slightly higher than the low
critical value.
•Low Critical - When the actual rating is below this value, a low critical alarm is sent.
6. Click Submit, then click Close.
When a threshold is met, an RPM software event is generated.
To monitor consistency (racks and rows of racks):
1. Click the Units tab.
2. Click Units in the top navigation bar.
3. Click Power Manager or Infrastructure in the side navigation bar.
4. Click on an infrastructure level or power device. The Unit overview window opens.
5. Click Power Manager in the side navigation bar.
6. Click Monitoring Consistency in the side navigation bar.
142Rack Power Manager Installer/User Guide