Technical data

Guide Specifications for Liebert Mini-Mate2- 5-Ton Systems
Liebert
®
Mini-Mate2
43
2.5.4 Condensate Pump Bracket
A condensate pump bracket shall be provided to mount condensate pump directly to the end of the
unit, allowing for easier installation and alignment of the condensate pump.
2.5.5 Refrigerant Line Sweat Adapter Kit
Provide a sweat adapter kit to permit field brazing of refrigerant line connections.
2.5.6 Single Point Power Kit
A single point power kit shall be provided for a close-coupled system to allow a single electrical power
feed to supply power to both the evaporator and indoor close-coupled condensing unit.
2.5.7 Liebert SiteScan
®
Site Monitoring System
A Liebert SiteScan Site Monitoring System Model ___________________________ shall be provided for
remote monitoring of the Liebert Mini-Mate2
unit and monitoring of other Liebert support
equipment. The Liebert SiteScan system shall have the capability to monitor and change (at the user
direction) the temperature and humidity setpoints and sensitivities of each unit. The printer shall
provide the user with chronological alarm information. It shall also be capable of being programmed
to print out environmental conditions or operating modes at each unit.
Provide indicated quantities of the following:
______ Leak Detection System(s) Model ______________________________________
______ Remote Monitor(s) Model _____________________________________+_______
______ Auto-changeover Control(s) Model _____________________________________
2.5.8 Drycooler
The Liebert drycooler shall be a low-profile, direct-drive propeller fan-type air-cooled unit. The
drycooler shall be constructed with an aluminum cabinet and a copper-tube aluminum fin coil and
multiple direct drive fans. All electrical connections and controls shall be enclosed in an integral
weather-resistant electric control panel section of the drycooler. The unit is quiet and
corrosion-resistant.
The drycooler shall be designed for _____°F (°C) ambient.
2.5.9 Glycol Pump Package
The system shall include a centrifugal pump mounted in a weatherproof and vented enclosure. The
pump shall be rated for ____ GPM (l/s) at ____ ft. (kPa) of head and operate on ____ volt, ___ phase,
____ Hz.