Technical data

Electrical Data
28 Liebert
®
Mini-Mate2
Table 19 Single-point power kit, air-cooled split system electrical data, optional 2hp motor
Base Evaporator Model
208-3-60 230-3-60 460-3-60 575-3-60 380/415-3-50
MMD60E/K MMD60E/K MMD60E/K MMD60E/K MMD590E/K
Base Condensing Unit Model
MCD65A MCD65A MCD65A MCD65A MCD64A
Cooling Only
FLA 32.3 32.3 15.8 12.0 17.4
WSA 37.5 37.5 18.3 13.9 N/A
OPD50502520 N/A
with Electric Reheat
FLA 60.1 57.4 28.4 22.0 31.8
WSA 72.2 68.9 34.1 26.4 N/A
OPD80804030 N/A
with Humidifier
FLA 42.1 41.2 20.2 15.5 22.5
WSA 47.3 46.4 22.7 17.4 N/A
OPD60603020 N/A
with Electric Reheat and Humidifier
FLA 60.1 57.4 28.4 22.0 31.8
WSA 72.2 68.9 34.1 26.4 N/A
OPD80804030 N/A
Base Evaporator Model
MMD60E MMD60E MMD60E MMD60E MMD590E
Base Condensing Unit Model
MCD65A MCD65A MCD65A MCD65A MCD64A
with SCR Reheat
FLA 73.9 70.0 34.6 N/A 39.1
WSA 89.5 84.6 41.8 N/A N/A
OPD909045N/AN/A
with SCR Reheat and Humidifier
FLA 83.7 78.9 39.0 N/A 44.2
WSA 99.3 93.5 46.2 N/A N/A
OPD 100 100 50 N/A N/A