Technical data

Electrical Data
Liebert
®
Mini-Mate2
27
Table 12 Electrical data—Split-evaporator or self-contained chilled water units, 50/60 Hz
Base Evaporator
Model Number
208/230 - 1Ph - 60Hz 277 - 1Ph - 60Hz 220- 1Ph - 50Hz
MM*12E; MM*18E; MM*23C MM*12E; MM*18E; MM*23C MM*22C
Cooling Only
FLA 1.4 1.4 1.4
WSA 1.8 1.8
OPD 15 15
with Electric Reheat
FLA20.217.720.2
WSA 25.3 22.1
OPD 30 25
with SCR Reheat
5
FLA20.217.720.2
WSA 25.3 22.1
OPD 30 25
with Humidifier
FLA 6.2 5.0 6.0
WSA 7.8 6.3
OPD 15 15
with Electric Reheat and Humidifier
FLA25.021.324.8
WSA 31.3 26.6
OPD 35 30
with SCR Reheat and Humidifier
5
FLA25.021.324.8
WSA 31.3 26.6
OPD 35 30
1. For units with Hot Water Reheat (available only on MM*22C & MM*23C), use appropriate values from “Cooling Only” or “with Humidifier”
categories.
2. FLA = Full Load Amps, WSA = Wire Size Amps, OPD = Maximum Overcurrent Protection Device
3. * = Specify “D” for disconnect, “0” for no disconnect.
4. Use MM*12E or MM*18E values for models with Free-Cooling options, except with SCR Reheat.
5. SCR Reheat not available with Free-cooling models.
Table 13 Electrical data—Outdoor PFH condensing units, 60Hz
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage
Phase
208/230-1
14 1
FLA 9.1
WSA 11.0
OPD 15
20 1.5
FLA 12.1
WSA 14.8
OPD 25
* FLA = Full Load Amps
WSA = Wire Size Amps (minimum supply circuit current capacity)
OPD = Maximum Overcurrent Protection Device (fuse or circuit breaker)