Technical data
Electrical Data
Liebert
®
Mini-Mate2
™
27
Table 12 Electrical data—Split-evaporator or self-contained chilled water units, 50/60 Hz
Base Evaporator
Model Number
208/230 - 1Ph - 60Hz 277 - 1Ph - 60Hz 220- 1Ph - 50Hz
MM*12E; MM*18E; MM*23C MM*12E; MM*18E; MM*23C MM*22C
Cooling Only
FLA 1.4 1.4 1.4
WSA 1.8 1.8 —
OPD 15 15 —
with Electric Reheat
FLA20.217.720.2
WSA 25.3 22.1 —
OPD 30 25 —
with SCR Reheat
5
FLA20.217.720.2
WSA 25.3 22.1 —
OPD 30 25 —
with Humidifier
FLA 6.2 5.0 6.0
WSA 7.8 6.3 —
OPD 15 15 —
with Electric Reheat and Humidifier
FLA25.021.324.8
WSA 31.3 26.6 —
OPD 35 30 —
with SCR Reheat and Humidifier
5
FLA25.021.324.8
WSA 31.3 26.6 —
OPD 35 30 —
1. For units with Hot Water Reheat (available only on MM*22C & MM*23C), use appropriate values from “Cooling Only” or “with Humidifier”
categories.
2. FLA = Full Load Amps, WSA = Wire Size Amps, OPD = Maximum Overcurrent Protection Device
3. * = Specify “D” for disconnect, “0” for no disconnect.
4. Use MM*12E or MM*18E values for models with Free-Cooling options, except with SCR Reheat.
5. SCR Reheat not available with Free-cooling models.
Table 13 Electrical data—Outdoor PFH condensing units, 60Hz
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage
Phase
208/230-1
14 1
FLA 9.1
WSA 11.0
OPD 15
20 1.5
FLA 12.1
WSA 14.8
OPD 25
* FLA = Full Load Amps
WSA = Wire Size Amps (minimum supply circuit current capacity)
OPD = Maximum Overcurrent Protection Device (fuse or circuit breaker)