Technical data
Electrical Data
Liebert
®
Mini-Mate2
™
25
9.0 ELECTRICAL DATA
Table 10 Electrical data, self-contained air-cooled units, 60Hz
Base Evaporator
Model Number
208/230 - 1Ph - 60Hz 277 - 1Ph - 60Hz
MM*12A MM*18A MM*12A MM*18A
Cooling Only
FLA 8.2 14.2 6.8 11.8
WSA 9.4 16.9 7.8 14.0
OPD 15 25 15 20
with Electric Reheat
FLA 27.0 33.0 23.1 28.1
WSA 32.9 40.4 28.2 34.4
OPD 35 45 30 35
with SCR Reheat
6
FLA 27.0 33.0 23.1 28.1
WSA 32.9 40.4 28.2 34.4
OPD 35 45 30 35
with Humidifier
FLA 13.0 19.0 10.4 15.4
WSA 14.2 21.7 11.4 17.6
OPD 15 30 15 25
with Electric Reheat and Humidifier
FLA 27.0 33.0 23.1 28.1
WSA 32.9 40.4 28.2 34.4
OPD 35 45 30 35
with SCR Reheat and Humidifier
6
FLA 31.8 37.8 26.7 31.7
WSA 37.7 45.2 31.8 38.0
OPD 40 50 35 40
1. Electrical values are not affected by hot gas reheat or free-cooling options
2. FLA = Full Load Amps, WSA = Wire Size Amps, OPD = Maximum Overcurrent Protection Device
3. * = Specify “D” for disconnect, “0” for no disconnect.
4. Self-contained air-cooled units include MM2CF blower box.
5. Hot Gas Reheat not available with Electric or SCR Reheat or Free-cooling options
6. SCR Reheat not available with Free-cooling models.