STEP 2 CONTINUED...
Mounting to a DIN Rail
Rail Mount Transmitter with Remote Mount Sensor
The least complicated assembly uses:
• a remote mounted transmitter
• an integral mount sensor with terminal block
• an integral style connection head
• a standard extension
• a threaded thermowell
Refer to the Metric Product Data Sheet (document number 00813-0101-2654) for complete
sensor and mounting accessory information.
To complete the assembly, follow the procedure described below.
1. Attach the transmitter to a suitable rail or panel.
2. attach the thermowell to the pipe or process container wall. Install and tighten the
thermowell before applying pressure.
3. Attach the sensor to the connection head and mount the entire assembly to the
thermowell.
4. Attach sufficient lengths of sensor lead wire to the sensor terminal block.
5. Attach and tighten the connection head cover. Enclosure covers must be fully engaged
to meet explosion-proof requirements.
6. Run sensor lead wires from the sensor assembly to the transmitter.
7. Attach the sensor and power leads to the transmitter. Avoid contact with leads and
terminals.
To attach the Rosemount 248H to a DIN rail, assemble
the appropriate rail mounting kit (part number
00248-1601-0001) to the transmitter as shown.
Transmitter
Mounting Hardware
Rail Clip