Brochures and Data Sheets

www.EmersonNetworkPower.com/ASCO
Emerson Network Power - Global Headquarters
1050 Dearborn Drive
Columbus, OH 43085
Tel: +1 614 888 0246
ASCO Power Technologies - Global Headquarters
50 Hanover Road
Florham Park, NJ 07932
800-800-ASCO
www.ascoapu.com
Switch Rating
Amps
Dimensions, In. (mm)
Width
Height
Depth
Approx. Shipping
Weight Lb. (kg)
30-100
150-225
7-15/16 (201)
7-15/16 (201)
8-5/16 (211)
9-1/2 (241)
3-1/2 (89)
3-1/2 (89)
6 (2.7)
7(3.2)
ASCO 920 Product Specifications
Switch Only (Panelboard Mounting)
1,2,3
1. Suitable insulation must be behind switch unit.
2. Suitable for bus bar mounting. Lugs not supplied.
3. Dimensional data is approximate and subject to change.
Certified dimensions available upon request.
Switch
Rating Amps
Dimensions, In. (mm)
Width
Height
Depth
Approx. Shipping
Weight Lb. (kg)
30-100
150-225
7-15/16 (201)
7-15/16 (201)
11-3/4(298)
14-1/2(368)
3-7/8 (98)
3-15/16(100)
8(3.6)
11(5.0)
Switch With Sub-Panel (Panelboard Mounting)
4
4. Enclosure gutter spaces are based on non-looping of cables within the enclosure. Where cables must be looped
within the enclosure, oversize cabinets are available at extra cost. Contact ASCO for complete information.
NEMA Type 1
Enclosure Dimensions, In. (mm)
Width
Height
Depth
13(330)
13(330)
18-1/4(464)
24(610)
4-1/2 (114)
4-1/2 (114)
Approx. Shipping
Weight Lb. (kg)
23(10.4)
31(14.0)
When Connected
1 Pole to Load
Ballast
Tungsten
General Use
277 VAC
250 VAC
347 VAC
480 VAC
250 VAC
600 VAC
Maximum Voltage Ratings at Rated Amps, Open or Enclosed
5
5. For DC service, maximum current rating is 75 amps or switch rating,
whichever is less, with maximum voltage rating of 125 volts
when connected 1 pole to load and 250 volts when
connected 2 poles to load.
Ballast
Tungsten
General Use
When Connected 2 Poles to Load on 1
and 3 Poles to Load on 3
Switch
Rating Amps
30-100
150-225
Inrush Current Values and Minimum
Recommended Control Circuit Fuse Size
6,7,8
6. Overcurrent protective device ratings for control circuits should be selected and installed in accordance with the NEC.
7. This table shows the minimum permissible control circuit fuse size, based on the operating coil’s momentary inrush current.
8. ASCO furnished control fuses are rated at 15 Amps.
120 Volts, 60 Hz
Inrush
Amps
24
30
8
10
240 Volts, 60 Hz
Minimum
Fuse
Inrush
Amps
12
15
4
5
Minimum
Fuse
277 Volts, 60 Hz
Inrush
Amps
11
13
4
5
480 Volts, 60 Hz
Minimum
Fuse
Inrush
Amps
6
7
Minimum
Fuse
2
3
Switch Rating
Amps
AL or CU
Terminal Lug
Wire Range
AWG-MCM
30
60-75
100
150-200
225
Wire Size for Service and
Control Connections
9,10
9. Control circuit connections are supplied with terminals
accommodate a copper wire range of #14 AWG to #10 AWG.
10. Service connection for switches on sub-panels are
furnished with solderless lugs to accommodate copper or
aluminum wire, except on 30 Amp size which is provided
with 1/4” studs.
No. of Cable
per Terminal
Lug Connector
14-8
12-2
14-1/0
6-250
4-400
1
1
1
1
1
Maximum Distance Between Control Station and One ASCO
920 RC Switch with Source Line Voltage at 90% of Normal
11
Switch Rating
Amps
AWG
No.
30-100
11. If the control device does not have adequate current-carrying capacity to control the
switch directly, or the control station is to be located a greater distance from the
switch than is allowed in the above table, auxiliary control relays for 2-wire, or 3-wire
control are available. See optional accessories on inside tab.
12. For 208 volt system, reduce 240 volt values by 15%.
13. For 265 volt system, reduce 277 volt values by 5%.
Distance in Feet
12,13
14
12
10
14
12
10
120 Volts,
60Hz
240 Volts,
60Hz
277 Volts,
60Hz
150-225
465
740
1175
395
630
1000
1860
2960
4700
1580
2520
4000
2480
3940
6265
2100
3350
5325
ASCO is the global leader in
power switching and controls
Emerson. Consider it Solved., Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2013 Emerson Electric Co. All rights reserved.
Publication 3206 R3 © September, 2013 Printed in the U.S.A.