Specifications

7000 Series Microprocessor Controller
Voltage and Frequency Sensing
Page 9
3-Phase under and over voltage settings on
normal and emergency sources.
Under and over frequency settings on normal and
emergency.
True RMS Voltage Sensing with +/- 1% accuracy;
Frequency Sensing Accuracy is +/- 0.2%.
Selectable settings: single or three phase voltage
sensing on normal and emergency; 50 or 60Hz.
Phase sequence sensing for phase sensitive loads.
Voltage unbalance detection between phases.
Status and Control Features
Time Delays
Output contacts for engine-start signals.
Selection between “commit/no-commit” on trans-
fer to emergency after engine start and normal
restores before transfer.
Advanced inphase algorithm which automatically
measures the frequency difference between the two
sources and initiates transfer at appropriate phase
angles to minimize disturbances from transferring
motor loads.
Event log displays 99 logged events with the time and
date of the event, event type and event reason.
Output signals for remote indication of normal and
emergency source acceptability
Statistical ATS/System monitoring data
screens which provide:
Total number of ATS transfers.
Number of ATS transfers caused by power
source failure.
Total number of days ATS has been in operation.
Total number of hours that the normal and
emergency sources have been available.
Engine start time delay - delays all engine starting
signals to override momentary normal source out-
ages - adjustable 0 to 6 seconds (can be extended to
60 minutes with external 24 volt DC source).
Transfer to emergency time delay - adjustable
0 to 60 minutes.
Emergency source failure time delay to ignore
momentary transients during initial generator set
loading - adjustable 0 to 6 seconds.
Retransfer to normal time delay with two settings:
Power failure mode - 0 to 60 minutes.
Test mode - 0 to 60 minutes.
Unloaded running time delay for engine
cooldown - adjustable 0 to 60 minutes.
Pre and post transfer signal time delay for selective
load disconnect with a programmable bypass on
source failures - adjustable 0 to 5 minutes. This sig-
nal can be used to drive a customer furnished relay,
or for (2) sets of double throw contacts rated 3 amps
at 480 volts AC, specify ASCO optional accessory
31Z.
Fully programmable engine exerciser with (7) seven
independent routines to exercise the engine genera-
tor, with or without loads, on a daily, weekly,
bi-weekly or monthly basis.
Contains all alarm signals, logic and time delays for
use with closed transition switches.
Insynch time delay - 0 to 3 seconds.
Failure to synchronize - 1 to 5 minutes.
Extended parallel - 0.1 to 1.0 seconds.
Delayed transition load disconnect time delay -
adjustable 0 to 5 minutes.
The same controller can be used for open, closed and
delayed transition control sequences.
Digital microprocessor.
Touch pad programming of features and settings with-
out the need for meters, variable power supplies and
reference manuals.
Sixteen (16) selectable operating voltages available in
a single Controller.
On-board diagnostics provide control panel and ATS
status information to analyze system performance.
Displays and counts down active timing functions.
Selectable multi-language display (English, German,
Spanish, French. For others contact ASCO).
Password protection to prevent unauthorized
tampering.
Serial communications board (RS-422/485 protocol)
for viewing adjustments and features with ASCO
PowerQuest communications products. Specify
optional accessory 72A.
Programmable load shed option for SYNCHROPOW-
ER
®
bus optimization applications. Specify optional
accessory 30B.