Specifications

Automatic Transfer Bypass-Isolation Switching
ASCO Automatic Transfer & Bypass-Isolation Switches are available in
open transition, closed transition and delayed transition designs. The
bypass and isolation features allow power transfer switches to be inspect-
ed, tested, and maintained without any interruption of power to the load.
Fig. 5 Bypass-Isolation Transfer
Switch rated 4 pole 2000 Amperes.
Transfer Switch Drawout Features (1000-2000 amperes)
Automatic secondary disconnects
remove all control power as switch
is withdrawn.
Drawout carriage provides for easy
transfer switch maintenance and/or
removal via commercially avail-
able breaker hoists.
For optional transfer switch lifting
yoke, specify accessory 82B.
For optional automatic shutters
which close when the transfer
switch is withdrawn to provide bus
isolation, specify accessory 82C.
Available 150 to 4000 amperes.
Bypass switch and transfer switch have identical electrical ratings.
Heavy duty mechanical interlocks prevent undesirable operation.
Bypass contacts carry current only during bypass mode.
Allows bypass-isolation without load interruption.
Transfer switch is drawout design for ease of maintenance.
Bypass and isolation handles are permanently mounted. The
bypass switch has dead front quick-make, quick-break operation
for transferring of loads between live sources.
Bypass switch is fully rated for use as a manual 3-position
transfer switch.
Bypass and isolation functions are simple, requiring a total of two
operating handles.
No toggle switches, push buttons, selector switches or
levers are required for bypass-isolation operation.
Mechanical flag indicators show bypass and transfer switch
positions.
Automatic
Secondary
Disconnects
Automatic
Shutters
(optional)
Fig. 6 Bypass-Isolation Transfer
Switch secondary disconnects
and optional automatic shutters.
Page 6
7000 Series Switching Solutions
Self
Aligning
Jaws
Fig. 7 Bypass-Isolation Transfer
Switch Self Aligning
power Jaws.