Withstand and Close-On Ratings for all 7000 Series Products
Notes: All values are available symmetrical RMS amperes and tested in accordance with the withstand and close-on requirements
of UL 1008. See publication 1128 for more information on withstand and close-on ratings for ASCO transfer switches.
Application requirements may permit higher withstand ratings for certain size switches (Contact ASCO).
* 150 amp 7000 Series in bypass-isolation configurations have higher WCR as indicated.
30 100,000 60 J 10,000 10,000 N/A
70, 100, 150 200,000 200 J 22,000 10,000 N/A
150*,260, 400 200,000 600 J 42,000 35,000 N/A
600, 800 200,000 1200 L 65,000 50,000 N/A
1000, 1200 200,000 2000 L 85,000 85,000 65,000
1600, 2000 200,000 3000 L 100,000 100,000 65,000
3000, 4000 200,000 6000 L 100,000 100,000 65,000
UL 1008 Withstand and Close-On Ratings at 480 Volts AC
Switch Rating Current-Limiting Max. Fuse Size Specific Breaker “Any” Breaker 30 Cycles Long Time
amps Fuse Rating amps types Rating Rating Withstand Ratings
Non-Automatic Transfer Switching
ASCO Non-Automatic Transfer Switches are
electrically operated units which are operated with
manual control switches mounted locally or at
remote locations.
Fig. 4 Non-Automatic operated, electrically
operated 400 ampere switch shown in
Type 1 enclosure.
• Sizes from 30 through 4000 amperes.
• Microprocessor based controller
provides for addition of optional
accessories.
• Controller prevents inadvertent oper-
ation under low voltage conditions.
• Low control circuit operating cur-
rents allow for long line runs
between remotely mounted manual
control switches and the transfer
switch.
• Source acceptability lights inform
operator if sources are available to
accept load.
• Standard inphase monitor can be
activated for transferring motor
loads.