Specifications

Withstand and Close-On Ratings for all 7000 Series Products
Notes: All values are available symmetrical RMS amperes and tested in accordance with the withstand and close-on requirements
of UL 1008. See publication 1128 for more information on withstand and close-on ratings for ASCO transfer switches.
Application requirements may permit higher withstand ratings for certain size switches (Contact ASCO).
* 150 amp 7000 Series in bypass-isolation configurations have higher WCR as indicated.
30 100,000 60 J 10,000 10,000 N/A
70, 100, 150 200,000 200 J 22,000 10,000 N/A
150*,260, 400 200,000 600 J 42,000 35,000 N/A
600, 800 200,000 1200 L 65,000 50,000 N/A
1000, 1200 200,000 2000 L 85,000 85,000 65,000
1600, 2000 200,000 3000 L 100,000 100,000 65,000
3000, 4000 200,000 6000 L 100,000 100,000 65,000
UL 1008 Withstand and Close-On Ratings at 480 Volts AC
Switch Rating Current-Limiting Max. Fuse Size Specific Breaker “Any” Breaker 30 Cycles Long Time
amps Fuse Rating amps types Rating Rating Withstand Ratings
Non-Automatic Transfer Switching
ASCO Non-Automatic Transfer Switches are
electrically operated units which are operated with
manual control switches mounted locally or at
remote locations.
Fig. 4 Non-Automatic operated, electrically
operated 400 ampere switch shown in
Type 1 enclosure.
Sizes from 30 through 4000 amperes.
Microprocessor based controller
provides for addition of optional
accessories.
Controller prevents inadvertent oper-
ation under low voltage conditions.
Low control circuit operating cur-
rents allow for long line runs
between remotely mounted manual
control switches and the transfer
switch.
Source acceptability lights inform
operator if sources are available to
accept load.
Standard inphase monitor can be
activated for transferring motor
loads.
Page 5
7000 Series Switching Solutions