FAQ
Why won't the generator shut-off?
Normal is unavailable (Check if the right voltage is supplied on the Normal lugs or if Normal Accepted
light is ON)
The generator is in cool down mode. Wait until the cool down timer times out.
The selector switch for manual engine start is set to run. Switch it to AUTO.
The TS (AUX1) auxiliary contact for engine start is stuck-up. Contact a service technician to calibrate
the cam switches.
The NR relay is damaged. Replace the Group 5 controller.
There is a problem on the generator.