FAQ
Normal OK
Load on Normal
SETTINGS
How do I change the password?
To change the password, follow the steps below.
1. Go to the Group 5 controller and press the
ESC button until the display shows (with normal
power available and the load connected to normal)
2. Press Enter/Save Settings. Then press
Menu Scroll until the display shows
3. Press Enter/Save Settings. Then
pressMenu Scroll until the display shows
4. If the password below shows “****”, you’ll
need to set DIP switch actuator no. 10 to
“Yes” first, before you can change the
entry.
5. Press Enter/Save Settings and change
the entry using the Increase Value
buttons. Press Enter/Save Settings to
save the entry.
6. After saving the entry, set actuator no. 10
back to “No” to enable the password.
How do I perform a transfer test?
To perform a transfer test, flip the momentary switch to the transfer test position and hold it for 15
seconds or until the switch actually transfers over.
How does the ATS work?
When referring to an open transition transfer switch, the transfer switch main contacts moves in a quick
break - before make mode transition. There is no momentary parallel connection of the two sources and
no extended center-off position during transfer. The transition is quick. The ATS controller monitors the
voltage and frequency of the two sources (upon re-transfer or any transfer between 2 “live” sources) and
ensures that they are in-phase before the load is transferred (if enabled).
How does the engine exerciser work?
The engine exerciser works by closing the engine start contacts and keeping it closed in order to crank and
run the generator. The engine start contacts are kept closed until the exerciser operation timer expires
(approximately 20 minutes). Controller signals the engine start contacts to open up and shut the generator
down completely (after the 5 minute engine cool down period).
For more information please refer to the User Guide.