Brochures and Data Sheets
Optional Features
•
Enclosures - Secure Double Door
-
UL Type 3R w/strip heater & thermostat
-
UL Type 4 or 4X
-
UL Type 12
•
Connections
-
Crimp lugs
-
Bus Riser on Normal, Emergency or Load
•
Protective Relays/Metering
-
Accessory
85L , see page 15
•
Surge Suppression
- Accessory 73, Surge protector (see pg. 14)
•
ASCO POWERQUEST
®
products (see pages 16-21)
- ASCO 72E Ethernet Connectivity module, page 17
- ASCO 5310/5350 Remote annunciators, page 17
- ASCO 5400 Power Quality Meters, page 17
•
Additional Breaker(s)
- Circuit Breaker on Emergency
- Load Distribution Panel
•
Optional high AIC ratings on breakers
Consult ASCO for additional features
7000 series Service Entrance Power Transfer Switches
The ASCO Service Entrance Power Transfer Switch
combines automatic power switching with a discon-
nect and overcurrent protective device on the utility
source. The power transfer switch meets all National
Electric Code requirements for installation at a facil-
ity’s main utility service entrance. Service entrance
rated transfer switches generally are installed at
facilities that have a single utility feed and a single
emergency power source. A circuit breaker serves
as the utility disconnect and links are provided to
dis-connect both neutral and ground connections.
This product is either UL 1008 or UL 891 listed and is
available up to 600V and 4000A in Standard, Delayed,
Closed Transition, Soft Load, and Bypass Isolation
Configurations.
8
Standard Features
• Available from 150 to 4000 Amperes
• ASCO 7000 SerieS Power Transfer Switch is
UL 1008 Listed
• Standard UL Type 1 Enclosure
• Disconnect and overcurrent protective device on
the utility source: molded case circuit breaker 150
to 2000 Amp; insulated case 3000 to 4000 Amp
• Disconnect link on Neutral
• Disconnect link on Ground
• Ground and Neutral Bus, all silver-plated copper
• Solderless screw type terminals for External
Power Connections
• Meets all NEC requirements for use as
service entrance
• Internet enabled monitoring and control
• Service entrance breakers are rated: -
100% for 1000 Amps and above; 80% below 1000
Amps for all bypass switches - 100% for 2500
Amps and above; 80% below 2500 Amps for all
standard transfer switches
Neutral
Disconnect
Link
Ground Disconnect
Link
Ground Fault
Current
Transformer*
Utility
Circuit
Breaker
ATS
Emergency
Load
N
Ø
N
Ø
GFCT -
Ground Fault
Current
Transformer
ATS - Automatic
Transfer Switch
Switched
Neutral
One line diagram of a typical service entrance rated transfer switch
available in Solid, Switched or Overlapping Neutral
* Ground fault trip protection provided on sizes of 1000 Amperes
and above
Fig. 13: Ground and neutral
disconnect links