Brochures and Data Sheets

15
Optional Configurations and
Connection Arrangements
Connected To: 5210 5220
Load Acc. 135L Acc. 85L
Normal Acc. 135L Acc. 85N
Emergency Acc. 135E Acc. 85M
Load (BPS only) N/A Acc. 85SB
*
Add suffix A1 to above metering designation if neutral conductor monitoring is required
Note: Accessory 85L and 135L includes component mounting, CTs, shorting
blocks and all necessary interwiring.
*Bypass & isolation switch contacts wired to discrete Power Manager inputs.
7000 series Optional Accessories
Power Metering
Voltage:
Line - Line: VAB, VBC, VCA, VAVERAGE
Line - Neutral: VAN, VBN, VCN, VAVERAGE
Frequency: 45.0 to 66.0 Hertz
Current: IA, IB, IC, IAVERAGE
Unbalance %: Voltage, Amps
Real Power: KWA, KWB, KWC, KWNET
Reactive Power: KVARA, KVARB, KVARC, KVARNET
Apparent Power: KVAA, KVAB, KVAC, KVANET
Real Energy: KWHIMPORT, KWHEXPORT, KWHNET
Reactive Energy: KVARHIMPORT, KVARHEXPORT,
KVARHNET
Power Factor: PFA, PFB, PFC, PFNET
5220 Power Manager Data Access
Eight digital inputs, four relay outputs.
Input/Output 15-character, user definable screen
display for identification of input/output signals.
Communications
Modbus RTU and TCP/IP capability
Ethernet compatible when combined with
5150 Connectivity Module (72E).
Fig. 19: ASCO 5210 SerieS
Power Meter.
Configurable Designations
Local - A four line, 20 character LCD backlit display.
5220 Power Manager provides user programmable setpoints
based on twelve metering and I/O parameters. Each setpoint
allows the user to select the parameter, the trip & reset levels,
the trip & reset time delays and the alarm type or relay output
to trigger. This can be used for protective relaying and peak
shaving applications.
100 event data logging feature.
Integrated ATS Features
When configured on load of ATS:
Displays ATS position.
Displays power data as a function of ATS position
(normal/emergency).
Accumulates energy data separately for normal and
emergency sources.
ASCO 5200 series Metering
Power Manager
The ASCO 5200 SerieS Power Meters are microprocessor
based metering devices that provides real-time measure-
ment of single and three phase power systems. The 5200
SerieS uses digital signal processing technology to measure
voltage and current per phase; real, reactive and apparent
power, and bi-directional energy. All measurements can be
viewed locally with a backlit liquid crystal display and/or
displayed remotely with ASCO POWERQUEST
®
products.
Direct voltage input for systems up to 600 Volts AC
can be monitored without the use of external potential
transformers (PTs). Measures three phase currents and a
fourth current input is available for measuring current
in the neutral conductor. The 5200 SerieS includes one
discrete input for transfer switch position.
Note: The ASCO Power Manager is also available as a separate unit for monitoring electrical parameters anywhere in the power distribution system.
Fig. 20: ASCO 5220 SerieS
Power Manager.