Installation Manual

Installation Manual ASCO 5350
Page 6 ASCO Power Technologies 381333-315 D
2-3 IP Address, Subnet Mask, Gateway
1. The default IP address parameter is: 169.254.1.200. If the
ATS Remote Annunciator is on a LAN enter the
appropriate IP address of the LAN. The default subnet
mask parameter is: 255.255.0.0, and the gateway address is
0 0 0 0
2. Write the IP address here __________________________.
3. Write the Subnet Mask here ________________________.
4. Write the Gateway Address here ____________________.
2-4 Port
The TCP/IP port must match the port used in the Connectivity
Module (manual 381333-238). The default port is 10001 for
ASCO Bus; port 502 is typically used for Modbus.
Write the port number here ________________________.
2-5 Encryption
Click Enable to turn on encryption, or click Disable to turn it
off. The default configuration is Disable (off). The
Connectivity Module must also have encryption selected.
Write which option is selected here_____________________.
This feature is only available with encrypted-enabled CMs.
All other devices communicating with the CM must be able to
read the encrypted data.
2-6 Audible Alarm (buzzer) Mode
Operation of the audible alarm and alarm relay (for external
buzzer) can be configured. In the Buzzer Mode list, click
Disable to turn it off (it will be inactive or silent even if an
alarm occurs). Click Periodic or Continuous to turn on the
audible alarm. The default setting is Continuous. See Figure
8. Write which option is selected here___________________.
Figure 8: Audible Alarm (buzzer) Mode
The buzzer sounds in one-second pulses (not adjustable).
In the Continuous mode the pulsing buzzer sounds
continuously (on-off cycles). In the Periodic mode the
duration of the pulses and interval between pulses can be set
as follows:
Duration (On Time) 0-2400 minutes
Interval (Off Time) 1-60 minutes
See Figure 9. Figure 10 shows the duration and interval
settings.
2-7 Buzzer On Time (duration)
Figure 9: Audible Alarm (buzzer) ON - OFF Times
Figure 10: Buzzer interval & duration settings
Buzzer total ON time: it is the total time in which the buzzer
ON-OFF cycle will repeat in periodic mode from the time the
buzzer alarm is initiated. This time period needs to be entered
in the Buzzer On time text box. The acceptable range of
Buzzer ON time is between 0 to 2400 minutes, fractional
values are not acceptable. Buzzer silences only if alarm
condition ceases or Buzzer On time elapses, which ever
occurs early.
2-8 Buzzer Off Time (interval)
If the Buzzer on time is set to zero, the buzzer ON-OFF cycle
repats infinitely unless the alarm condition ceases or silence
alarm key is pressed.
The period of each buzzer ON-OFF cycle: It is the period after
which the Buzzer ON-OFF cycle repeats. This time period
needs to be entered in the Buzzer Off time text box. The
acceptable range of the period is between 1 to 60 minutes.
Fractional values are not acceptable. ON time in each of these
cycles is fixed at one second.
2-9 Click Update to Save Configurations !
Be sure to click UPDATE to save the configuration
settings and upload them to the ATS Remote
Annunciator.