Installation Manual
Installation Manual ASCO 5350
Page 4 ASCO Power Technologies 381333-315 D
Functional Test
After installing the ATS Remote Annunciator communication
must be established to configure it. A Windows-based laptop
computer is needed. You must have access to the other end of
the communication cable that is connected to the ATS Remote
Annunciatior. You also need to know the factory default
settings on the label (see page 2).
1 Initial checks
After the ATS Remote Annunciator is mounted and wired
(both power and communication) perform these tests:
1. Turn on the power to energize the ASCO 5350.
2. Verify that the power light is illuminated (upper right).
3. Turn the Control key switch to the right (unlocked).
4. Press the lamp test button (below the power light); all
lights should illuminate.
2 Communication check
A laptop computer running Windows Xp and Internet Explorer
5.0 + will be used in these steps to configure the ATS Remote
Annunciator. You will need to temporarily disconnect the
other end of the communication cable from the ATS Remote
Annunciator and connect it instead to the laptop computer.
1. Connect the Ethernet cable from the ATS Remote
Annunciator to the laptop computer’s Ethernet jack.
2. Start Windows, click the Start button, then Control Panel.
3. Double click the Network Connections icon.
4. Double click the Local Area Connections icon, then click
Properties.
5. Select Internet Protocol (TCP/IP), then click Properties.
6. Set the IP setting of the laptop computer (see Figure 2):
IP Address 169.254.1.100 (last digit must be
different than ASCO 5350 Default IP)
Subnet Mask 255.255.0.0 (same as ASCO 5350)
Default Gateway leave blank
(This is needed only if communicating to a different LAN.)
7. Click OK and click Close. Close the Local Area
Connection window.
8. Once the TCP/IP setup is complete at the laptop computer,
restart the computer (click Start button, then click
Restart).
9. Restart Windows, then click the Start button. Select All
Programs > Accessories > Command Prompt.
10. In the command prompt window type ipconfig and press
ENTER. The settings are displayed.
11. In the command prompt window type
ping 169.254.1.200 and press ENTER.
You should see: Reply from 169.254.1.200
This reply confirms communication between the laptop
computer and the ATS Remote Annunciator. Close the
command prompt window. Proceed to the Configuration,
Login screen on page 5.
Figure 2: Internet protocol
2-1 Login Names
See page 5. Two predefined login names are provided:
admin for administrator (can change configuration and
diagnostic functions).
user can only see diagnostic screens in the web interface. The
user cannot change any configurations.
2-2 Change Password
See page 5. The default password is on the label ( ASCO ).
To change the password, click Change Password. The
password can be up to 15 characters (do not use spaces). You
can set only one password. Type in the Old Password, the
New Password, and Retype [new] Password. Then press OK
to save it. If you make a mistake click Reset and start over.
Figure 3: Change password screen