Operation
The ASCO 5310 ATS Remote Annunciator communicates
with an ASCO automatic transfer switch (ATS) to report its
status. The ATS Annunciator polls the ATS and obtains its
status. Lights indicate if the ATS is connected to the normal
source or the emergency source. Source acceptability status
for the ATS is also shown. In addition, the ATS Remote
Annunciator can send commands to the ATS to control its
operation.
A control key switch prevents unauthorized operation. A
transfer test button simulates a normal source outage and
transfers the load to the emergency source, if acceptable. The
same button is used to retransfer the load back to the normal
source. When the button is held, any active time delay is
cancelled. A lights in the button indicates if the ATS is in the
test mode and if a time delay is active. See Figures 1 and 2.
Figure 2: Control buttons
1 Control key switch
The Control key switch prevents unauthorized operation of
the ATS Remote Annunciator. The key can be removed in
either the locked or unlocked positions. In the locked position
(left), the buttons do not operate. In the unlocked position
(right) all buttons function.
2 Alarm silence button
Press and release the alarm silence button to turn off the
audible alarm sound. Do not hold the button. These are the
possible alarm conditions:
Alarm Condition Product
communication error
185, 300,
4000, 7000
locked out 4000 & 7000
ATS position error 4000 & 7000
failure to synchronize 4000 & 7000
extended parallel 4000 & 7000
controls not in automatic 4000 & 7000
ATS bypass active 7000
Alarms can be specific to the ATS or a general (common)
communications error or any configured alarm via the Power
Manager.
Before using the transfer button, be sure conditons
are safe for running the generator and for load
transfer.
3 Transfer test
The following operation starts the generator and transfers the
load. Be sure that conditions are safe to do this operation.
3-1 Load Transfer to Emergency source
To transfer the load from the normal source to the emergency
source, follow this procedure:
1. Turn the Control key right to the unlocked position.
2. Press and release
Transfer button (do not hold the
button).
3. Observe that the generator light comes on (generator
acceptable).
4. Observe that the light in the corner of the button blinks
(transfer time delay active, if used).
5. Observe that the ATS connected lights change position
(transfer from normal to emergency).
6. To retransfer the load back to Normal go to section 3-2.