Brochures and Data Sheets

9
4000 S
ERIES USER INTERFACE
User Interface Features
Convenient
One
Line
Diagram
- Provides a clear view of
the position of the transfer switch, as well as the
acceptability of the Normal and Emergency sources.
Source
Acceptability
LEDs
- Provide true indication of the
acceptability of each source, as determined by the volt-
age, frequency, voltage unbalance, and phase sequence
settings of the control panel.
Transfer
Switch
Position
LEDs
- Provide an indication of
which source the transfer switch is connected to.
Transfer
Test
-
Allo
ws the user to test the operation of
the transfer switch under a simulated failure of the nor-
mal source. Holding for 15 seconds allows time for the
engine generator to come online and the transfer
switch to transfer the load.
Retransfer
to
Normal
-
Allows the user to bypass the
programmed Retransfer to Normal time delay upon the
return of the normal source when the switch has trans-
fered to emergency either during normal operation or a
transfer test.
Lamp
Test
- Provides a convenient way to verify the
functionality of all LEDs on the User Interface.
User
Controls
Locked
- Visually displays the status of
the keypad lock feature of the control panel. When
illuminated, the buttons of the User Interface are
disabled and the user must enter a password into the
control panel to unlock the switch. When LED is blink-
ing, the controls are temporarily unlocked for five
minutes from the last button pressed.
Additional Closed Transition User
Interface Features
Extended
Parallel
Time
- Provides visual indication when
the pre-set extended parallel time has been exceeded.
The controls automatically open the emergency or nor-
mal main contacts. Separate contact also available to
shunt trip to an external breaker.
Failure
To
Synchronize
- Visually displays a failure to syn-
chronize alarm if the time delay settings is exceeded,
during closed transition transfer operation.
Transfer
Switch
Locked
Out
- Prevents transfer in either
direction if the extended parallel time is exceeded.
Alarm
Reset
- Resets extended parallel and failure to
synchronize alarms.
Closed
Transition
Bypass
- Pu
shbutton allows transf
er
between sources in an open transition mode.
Fig.
8:
4000 SERIES Closed Transition User Interface
Fig.
7:
4000 S
ERIES Open Transition User Interface