User Guide

Programming Battery Setup for the MPM
17-11
17.6. Battery Setup: Digital Input (MPM)
String View > Setup|Battery|Digital Input
The MPM has 16 digital inputs that may be connected to external dry contacts. You may set
up these inputs on the Digital Input dialog box to report an alarm when the external contacts
are activated.
Figure 57. Battery Setup - Digital Input (MPM)
Input Name - Assign a name to the input connected to the external contacts and indicate if
the contacts are normally open or normally closed. To disable an input, clear the input name.
N/C or N/O - Select the N/C box if the external contacts are normally closed. Select the N/O
box if the external contacts are normally open.
Report - Selecting this check box lets the monitor report a digital input alarm. When not
selected, reporting is disabled for that input.