Brochures and Data Sheets
4200-062 12 Revision 2.01
Alarmreset.Normally‐opendrycontactrequired.
*Optionaltemperatureandcurrenttransducersarerequired.
Actualnumberofinputsaremodeldependent.ContactAlberforadditionalinformation954‐623‐
6660.
Outputs
ThreeprogrammablerelaycontactconfiguredtoN/OorN/C
Parametersalarmcontact:oneFormCalarmrelaycontact,2Aat30VDC.
Hardwarefailureor
powerfailurealarmcontact:oneFormCalarmrelaycontact,2Aat30VDC.
Chargercontrolrelay:oneNOdrycontact,2Aat30VDC.
LEDs(oneeach):greenstatus,redalarm,redalarmdisable,greenresistanceteston,andred
hardwareerror.
MeasurementRange/Tolerance
Cellresistance............................0to32,000µ........5%ofreading±1
Communication
AUSBport
Amodemserialport
AnRJ‐45connectionorRS‐232portconnection
Protocols:ModbusandSNMP.
DataStorage
E
2
nonvolatilememoryforcalibrationconstants,alarmlevels,telephonenumbers,andsetup
information.
100alarmeventsinrevolvingnonvolatilememory.
32Kbytesofdischargedatainnonvolatilememory.
1.6Kbytesresistancetestrecords.
1.65Kbyteshistoricaldata.
Flashmemoryforfirmwareupgrades.
OperatingEnvironment
Temperaturerange:5Cto40C(41Fto104F)
Humidityrange: 0%to80%RH(noncondensing)at5Cto31C
0%to50%RH(noncondensing)at32Cto40C
Indooruseonly.
InstallationcategoryII
Pollutiondegree2.
Altitude0to2000metersabovesealevel.
Packaging
Rackmount.
Wallmountwithoptionalmountingbrackets.
Dimensions
19"Wx10"Dx1.75"H
6lbs.