Brochures and Data Sheets
389 MPM‐100‐1x100x1 1stringof100–1vcellsinseries.
387 MPM‐100‐1x54x2 1stringof54–2vcellsinseries.
409 MPM‐100‐1x56x2 1stringof56–2vcellsinseries.
397 MPM‐100‐1x58x2 1stringof58–2vcellsinseries
357 MPM‐100‐1x60x2 1stringof60–2vcellsinseries.
358 MPM‐100‐1x30x4 1stringof30–4vmodulesinseries.
391 MPM‐100‐1x18x6 1stringof18–6vmodulesinseries.
359 MPM‐100‐1x20x6 1stringof20–6vmodulesinseries.
376 MPM‐100‐1x15x8 1stringof15–8vmodulesinseries.
377 MPM‐100‐2x15x8 2stringsinparallelof15–8vmodulesinseries.
390 MPM‐100‐1x8x12 1stringof8–12vmodulesinseries.
412 MPM‐100‐2x9x12 1stringof9–12vmodulesinseries.
356 MPM‐100‐1x10x12 1stringof10–12vmodulesinseries.
Figure16.MPM60V‐120VSystemsConfigurationOptionsChart
4. MPM-100 Specifications
Power
15wattsmaximum.Whenmonitoring24Vto48Vbatteries,operatesdirectlyfromthebus.
Whenmonitoring120VDCbatteries,poweredoffthebatteryora115VACwallplugtransformer.
Thetransformermustbeonaprotected(uninterruptible)powersource(UPS).
WallPlugTransformer:Albérpartnumber4000‐029
Input:
100to240VAC,50Hz/60Hz,1.0Amaximum
Output:24VDC(nominal),1.5A36Wmaximum
4.1. Fuses On PC Board (Not user replaceable)
FuseF1/F1A:2AFB.
FuseF2:1AFB.
FuseF3:0.5AFB.
4.2. Measurement Range/Inputs
Inputs Range Tolerance
100cellvoltagechannels
2Vrange............(0‐4V)...................0.1%1mV
4Vrange............(0‐8V)...................0.1%2mV
6Vrange............(0‐8.5V)................0.1%2mV
8Vrange............(0‐10V).................0.1%10mV
12Vrange............(0‐16V).................0.1%10mV
Onestringvoltagechannel...............0to150volts.........0.1%ofreading0.1V
Eighttemperaturechannels*...........0Cto80C(32Fto176F)1C
Eightintertierresistancechannels...0to5m................5%ofreading5
Fourdischargecurrentchannels*....0to4000A..............0.1%ofreading1A(usingshunt)
Fourfloatcurrentchannels*............0to5000mA..........50mA
Sixteenopticallyisolatedcontactclosureinputsfornormally‐openornormally‐closed.