Brochures and Data Sheets
LocalPort
J2
J5
J1,J3,J4,J6,J7
MaybeanRS–
232oranRJ–
45network
port(LAN).The
frontpanel
LocalPort
Switchenables
thisport.
Providesforalarm(Parameter&
System)&digitalinputrelay
connectionsonallMPM
configurations.Twosetsofdry
FormCalarmcontactsarealso
available.
Donotuseforcurrent
transducersifJ5isavailable.
CurrentTransducerCT
connector–optional.
Providesforsignal
connectionand+15V
and–15Vpowerforup
to4dischargeCTsand
signalconnectionforthe
FloatCurrentSensor.
Senseleadwiringtothese
connectors–Dependsupon
batteryconfiguration.
Cell/Jarvoltagesenseleads
connect
fromJ1tothe
individualcells/jars.(&J3
onunitswiththeexpansion
module)
TELCO LoadConnections
16to20,11to15,6to10,1to5
Input24VDC1.2A
RJ–11jack.
Communicates
witharemote
computervia
telephone.
Themost–positivebatteryconnection
forstring1mustalwaysbetoLoadConnection
#1.Thenegativeconnection
isdeterminedbythebattery
configuration.
WhentheMPMrequiresACpower
becauseofbatteryconfiguration,
connecta24VDCwallplugtransformer
tothisconnector.
ACpowermustbe
fromaUPSprotectedsource.
Figure12.RearPanelConnectors