User Guide

BDSi Data Collection Module Specifications
4200-077 R3.4 14 6/19/2013
Float current:
0 to 5000mA ±50mA.
Optional current transducer required. Transducer accuracy
affects overall current reading accuracy.
5.7 Communications
Fiber optic,
Albér proprietary
5.8 Data Storage
E
2
nonvolatile memory for setup
Flash memory for firmware upgrades
5.9 Control Switches
DIP switch (rear panel) for setting string identification
5.10 Operating Environment
Temperature
range:
5C to 40C (41F to 104F)
Humidity range:
0% to 80% RH (non condensing) at 5C to 31C
0% to 50% RH (non condensing) at 32C to 40C
Indoor use only
Installation category I
Pollution
degree 2.
Altitude 0 to 2000 meters above sea level
5.11 Dimensions
19.5"W x 12.06"D x 5.09"H
12 lbs.
5.12 Agencies
UL recognized. File number E212234
CE approved