Brochures and Data Sheets
Liebert NXL battery cabinet with Alber
BDSi Battery Monitor. First battery
cabinet (center) with Controller and
DCM/LM. Additional battery cabinet
(right) with DCM/LM only.
Liebert APM battery
cabinet with DCM/LM
(top) and Controller
(bottom)
The Alber BDSi system consists of two units: a Controller, and a Data Collector
Module/Load Module (DCM/LM).
The rst battery cabinet includes both an Alber BDSi Controller and Alber BDSi
DCM/LM. Each additional battery cabinet uses only an Alber BDSi DCM/LM unit
linked to the single Controller Unit in the rst battery cabinet. A Controller can
communicate with up to six DCM/LM units or battery cabinets. Communication
options are by Ethernet network card, RS-232 or dial-up modem.
The Alber BDSi
Controller stores
the data, provides
alarms, power and
communication
connections
Simple hardware conguration
User-friendly software
provides easy to
interpret data
Battery Monitor Data
Manager (BMDM) Computer
Software is included with
every system. With the
software you can program
thresholds, view graphs
and trends to identify
failing batteries, set alarms
notications and distribute
reports. The reports have
built-in decision support
that analyzes the data and
provides suggestions for the
best corrective action.
The DCM/LM unit collects individual cell
data and performs the resistance test.
Easy to interpret graphs
make data understandable
and manageable