User Guide
Commissioning Assistant
29-8
29.4.6. Serial Numbers Screen
Figure 144. Serial Numbers (Comm Asst)
Click the Serial Numbers button. To upload the serial numbers and firmware revisions
from the connected hardware, click the Upload button. If the data is incorrect, click in the
field to type the correct data and click the Change button to send the data to the hardware.
The RTM and ELM serial numbers must be typed in manually.
29.4.7. Check Cell Voltage Screen
Figure 145. Check Cell Voltage (Comm Asst)
Click the Check Cell Voltage button. Measure the voltage across the cell indicated, type the
value in the Measured Value field, then press <Enter>. If the measured value agrees with the
calculated value in the monitor, the Status area indicates Passed. If it fails, calibrate the
monitor to the measured value by clicking the Cal button. Note that, if there is a more
convenient cell to measure, you may change the Cell Number to any cell within the DCM.