User Guide

Commissioning Assistant
29-7
29.4.4. Send Battery Setup Screen
Figure 142. Send Battery Setup (Comm Asst)
Click the Send Battery Setup button. Verify the values displayed on the screen, make
changes if necessary, then click Send to transfer the settings to the monitor. Note that event
recording is ignored and the system doesn't alarm during commissioning. Alarms are disabled
until the base resistance thresholds are sent. If using string current for discharge detection, the
minimum value that can be entered is 5 percent of the shunt value.
29.4.5. Check Settings Screen
Figure 143. Check Settings (Comm Asst)
Click the Check Settings button. Confirm the values, then click Yes to upload the
calibration constants from the monitor to the database. If you click Recheck, the screen
refreshes. NOTE: Only the calibration constants are uploaded.