User Guide
Using the Report Generator
22-6
Data Sets area - To manually select cells to include in the report, click the cells in the list or
click All to select all items. If Auto Select Cells is selected, cells that violate thresholds are
already selected. To clear all selected items, click None. If the BMDM was used with an
MPM, the list shows string and cell. If a BDS was used, the list shows cell only. If the
selected range contains no data, no cells appear under Data Sets.
22.5. Trend Cell Resistance Report
String View > View|Reports|Trend|Cell Resistance
To create a Trend Cell Resistance report, click Cell Resistance. The Trend Cell Resistance
Setup box appears.
Figure 100. Trend Cell Resistance Setup
The items on the Trend Cell Resistance Setup box are the same as those in Trend Cell
Voltage Report, with the following exceptions.
To ignore BMDM thresholds, click Override Preset Thresholds. In the Baseline box, type
the resistance in microhms. In the % Above Baseline box, type the percentage above which a
measurement will be in violation. For example, if the baseline resistance is 300 microhms and
the percentage is 10%, any data above 330 microhms violates threshold.
Select Show Average Trend to generate a graph that shows the average cell resistance over
the range of dates.