User Guide
Commissioning Assistant
31-11
31.4.13. Check Discharge Current Screen
Figure 169. Check Discharge Current (Comm Asst)
Click the Check Discharge Current button. Verify the ±15VDC voltage supply is
connected to the current transducer. Type the discharge current value in the Measured Value
field. The String Current (amps) field displays the millivolt value times the shunt value as
amps. If the measured value agrees with the calculated value in the monitor, the Status area
indicates Passed. If the measured value fails, calibrate the monitor to the measured value by
clicking the Cal button.
31.4.14. Check Test Current Screen
Figure 170. Check Test Current (Comm Asst)
Click the Check Test Current button. Before running this test, verify that all the voltages
across the load wires are correct. Failure to do this may result in severe damage to the load
module.