User Guide

Commissioning Assistant
31-10
31.4.11. Check Float Current Screen
Figure 167. Check Float Current (Comm Asst)
Click the Check Float Current button. Type the float current value in the Measured Value
field, then press <Enter>. If the measured value agrees with the calculated value in the
monitor, the Status area indicates Passed. If the measured value fails, calibrate the monitor to
the measured value by clicking the Cal button.
31.4.12. Check Temperature Screen
Figure 168. Check Temperature (Comm Asst)
Click the Check Temperature button. Type the ambient temperature value in the
Measured Value field. If the measured value agrees with the calculated value in the monitor,
the Status area indicates Passed. If the measured value fails, calibrate the monitor to the
measured value by clicking the Cal button.