User Guide

Commissioning Assistant
31-6
Click the Post Power Check button. Verify the DCM addresses by clicking “Run DCM
Addr Check” button then, at the “Running DCM Address Check” message click Yes to check
all DCM addresses. Also, clear the data memory by clicking the “Clear Memory” button then,
at the "Clear Monitor Memory" message click Yes and the memory is cleared. After
verification, the DCM Addresses Verified box is automatically checked.
Note: The MPM does not have dip switch settings.
31.4.4. Send Battery Setup Screen
Figure 160. Send Battery Setup (Comm Asst)
Click the Send Battery Setup button. Verify the values displayed on the screen, make
changes if necessary, then click Send to transfer the settings to the monitor. Note that event
recording is ignored and the system doesn't alarm during commissioning. Alarms are disabled
until the base resistance thresholds are sent. If using string current for discharge detection, the
minimum value that can be entered is 5 percent of the shunt value.