User Guide

Using the Report Generator
24-11
Select Tabular to create a Tabular report, which is the same as a standard report, but in a
spreadsheet format, with Cells vs. Time.
Click Cell Graph to create a report that includes a cell graph.
Click Cell Detail to create a report that includes cell detail.
Click OV/I Graph to create a report that includes Overall Voltage and Load Current graphs.
The Discharge Dates columns list the Start Date/Time, Duration, Lowest OV, OV@30 and
ACV@30 of all discharges. The Lowest OV column lists the lowest value reached during
discharge. OV@30 lists the overall voltage 30 seconds into discharge, and ACV@30 lists the
average cell voltage 30 seconds into discharge. Click the discharge for which the report will
be generated. Only one discharge date may be selected for a report.
Cell Detail area - To manually select cells to include in the report, click the cells in the list or
click All to select all items. If Auto Select is selected, cells that violate thresholds are already
selected. To clear all selected items, click None. If more than one subdirectory of cell data is
available, tabs for each subdirectory appear above the list of cell names.
24.11. Alarm Report
String View > View|Reports|Alarm
To create an Alarm report, click Alarm. The Alarms Setup box appears. Options selected on
Alarms Setup are saved by the battery name.
Figure 124. Alarms Setup
Select Include String Memos to include string memos in the report.
Alarm Types area - Alarm types that you may include in the report are high and low overall
voltage, high intertier resistance, high and low cell voltage, high cell resistance, and high and
low temperature. Select these items to include full details of each alarm, not just a summary.
If Digital I/O is selected, the system generates an alarm if a digital input is selected on the
battery setup digital output screen.